2022 High quality Zirconia Oxygen Analyzer - Nernst N2001 oxygen analyzer – Litong
2022 High quality Zirconia Oxygen Analyzer - Nernst N2001 oxygen analyzer – Litong Detail:
Application range
The Nernst N2001 oxygen analyzer is widely used in the detection of oxygen content in the combustion process of electric power, metallurgy, steel, chemical industry, ceramics, incineration, etc.It can also directly monitor the oxygen content in the flue gas of boilers, kilns, sintering furnaces, heating furnaces, pit annealing furnaces, etc. during or after combustion.During the measurement, the temperature in the furnace and the flue can be from normal temperature to 1400°C high temperature.The oxygen analyzer provides real-time oxygen content O2% (percentage) parameters and oxygen potential millivolt values in the furnace or flue.
Technical characteristics
• Input function: One oxygen analyzer can be connected to a oxygen probe to display the measured oxygen content in real time.
• Multi-channel output control: the analyzer has one 4-20mA current output and network communication interface RS485.
• Measurement range: The oxygen measurement range is 0 to 100% oxygen.
• Alarm setting: The analyzer has 1 general alarm output and 3 programmable alarm outputs.
• Automatic calibration: The analyzer has an automatic calibration function, and the user can customize the calibration time and number of calibrations according to their needs.
• Automatic dust cleaning: The analyzer has the function of automatically cleaning the probe. The user can clean the probe regularly according to the needs, eliminating the need for manual on-site dust cleaning.
• Intelligent system: The analyzer can complete the functions of various settings according to the predetermined settings.
• Display output function: The analyzer can display the date, current oxygen content, probe temperature, current oxygen millivolt value and 14 first-level status displays and 11 second-level status displays.
• Safety function: When the furnace is out of use, the user can control to turn off the heater of the probe to ensure safety during use.
• Installation is simple and easy: the installation of the analyzer is very simple and there is a special cable to connect with the zirconia probe.
Specifications
Inputs
One zirconia oxygen probes or sensors
Outputs
Linear 4~20mA DC
Display mode
128×64 dot liquid crystal display
Probe heating method
PID control
Dust cleaning and standard gas calibration
The analyzer has an automatic calibration function and an automatic dust cleaning function.It can also automatically control the solenoid valve switch.
ary Parameter Display
AlarmsParameter Display
High and low oxygen alarms can be set arbitrarily.
AccuracyP
± 1% of the actual oxygen reading with a repeatability of 0.5%.
Reaction rateP
Indirect heating measurement is about 3 seconds
Direct heating in 30 seconds
Core detection reaction speed: 0.0001s
Range of Local Indication
0 to 100% Oxygen
Serial/Network Interface
RS232
RS485 MODBUSTM
Reference gas
There is a miniature brushless motor vibration pump in the analyzer for reference gas.
Power Ruireqements
85VAC to 264VAC 3A
Operating Temperature
Operating Temperature -25°C to 55°C
Relative Humidity 5% to 95% (non-condensing)
Degree of Protection
IP65
IP54 with internal reference air pump
Dimensions and Weight
300mm W x 180mm H x 100mm D 2.5kg
Product detail pictures:
Related Product Guide:
To create much more benefit for consumers is our company philosophy; customer growing is our working chase for 2022 High quality Zirconia Oxygen Analyzer - Nernst N2001 oxygen analyzer – Litong, The product will supply to all over the world, such as: New Zealand, Hamburg, USA, We've customers from more than 20 countries and our reputation has been recognized by our esteemed customers. Never-ending improvement and striving for 0% deficiency are our two main quality policies. Ought to you want anything, don't hesitate to contact us.
By Mario from Tunisia - 2017.09.22 11:32
As a veteran of this industry, we can say that the company can be a leader in the industry, select them is right.
By Bella from South Africa - 2017.07.07 13:00